Daikin EWAQ006BAVP Installer's Reference Manual page 52

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ006BAVP:
Table of Contents

Advertisement

8 Configuration
Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
LWT setpoint mode:
▪ 0 (Fixed)
The
temperature is:
▪ NOT weather-dependent (i.e. does
▪ fixed in time (i.e., NOT scheduled)
▪ 1 (Weather dep.) (default): The
desired leaving water temperature is:
▪ weather-dependent (i.e. depends
▪ fixed in time (i.e., NOT scheduled)
#
Code
[A.3.1.1.1]
N/A
<< continuation
▪ 2 (Fixed/scheduled): The desired
leaving water temperature is:
▪ NOT
▪ according
▪ 3
leaving water temperature is:
▪ weather-dependent
▪ according
#
Code
[7.7.1.1]
[1-00]
Set weather-dependent heating:
T t
[1-01]
[1-02]
[1-02]
[1-03]
[1-03]
▪ T
(main)
▪ T
Installer reference guide
52
Description
desired
leaving
water
NOT
depend
on
the
outdoor
ambient temperature)
on
the
outdoor
ambient
temperature)
continued >>
Description
weather-dependent
does NOT depend on the outdoor
ambient temperature)
a
schedule.
scheduled
actions
consists
desired shift actions, either preset
or custom.
Remark: This value can only be
set in leaving water temperature
control.
(WD/scheduled):
The
desired
(i.e.,
does
depend on the outdoor ambient
temperature)
a
schedule.
scheduled
actions
consists
desired
leaving
water
temperatures
either
preset
custom.
Remark: This value can only be
set in leaving water temperature
control.
Description
[1-00]
[1-01]
: Target leaving water temperature
t
: Outdoor temperature
a
continued >>
#
Code
[7.7.1.1]
[1-00]
[1-01]
[1-02]
[1-03]
(i.e.,
#
Code
The
of
[7.7.1.2]
[1-06]
[1-07]
[1‑08]
[1-09]
The
of
or
T a
Packaged air-cooled water chillers and packaged air to water heat
Description
<< continuation
▪ [1-00]:
Low
outdoor
temperature. –40°C~+5°C (default: –
10°C)
▪ [1-01]:
High
outdoor
temperature.
10°C~25°C
15°C)
▪ [1-02]:
Desired
leaving
temperature
when
the
temperature equals or drops below
the
low
ambient
[9‑01]°C~[9‑00]°C (default: 45°C)
Note: This value should be higher
than [1-03] as for low outdoor
temperatures
warmer
required.
▪ [1-03]:
Desired
leaving
temperature
when
the
temperature equals or rises above
the
high
ambient
[9‑01]°C~min(45, [9‑00])°C (default:
35°C)
Note: This value should be lower
than [1-02] as for high outdoor
temperatures less warm water is
required.
Description
Set weather-dependent cooling:
T t
[1-08]
[1-09]
[1-06]
[1-07]
▪ T
: Target leaving water temperature
t
(main)
▪ T
: Outdoor temperature
a
EWAQ+EWYQ006+008BAVP + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
4P492901-1 – 2017.06
ambient
ambient
(default:
water
outdoor
temperature.
water
is
water
outdoor
temperature.
T a
continued >>