72
Appendix 1 Parameter Set
Para.
Name
Motor overload
FL.00
protection
Motor overload
FL.01
protection factor
FL.02
Stall over voltage
Stall over voltage
FL.03
point
Overload detection
FL.04
config
Overload detection
FL.05
threshold
FL.06
Overload alarm delay 0.0~60.0s
Auto current limiting
FL.07
threshold
Freq.decrease rate
FL.08
rate during current
limiting
Action mode of auto
FL.09
current limiting
FL.10
Auto reset times
FL.11
Auto reset interval
Protective action
FL.12
mode 1
Protective action
FL.13
mode 2
Group FL: Protection Parameters
0: disabled
1:Common motor (with low speed compensation)
2: Variable frequency motor (without low speed compensation)
20.0~110.0%
0: disabled (when braking resistor installed)
1: enabled
380V: 120.0~150.0%
220V: 110.0~130.0%
One's place of FL.04: overload detection mode
0: the detection is done as long as the drive is operating.
1: the detection is done only when the drive works at constant
speed.
Ten's place of FL.04: action mode
0: The overload is ignored, no alarm.
1: During "Overload Alarm Effective Period", the drive will alarm
and stop operation.
Hundred's place of FL.04: reference current
0: the overload detection threshold (FL.05) is set based on
motor's rated current. Fault code E014.
1: the overload detection threashold (FL.05) is set based on
drive's rated current. Fault code E013.
G type: 20.0%~180.0%
P type: 20.0%~130.0%
G type: 20.0%~180.0%
P type: 20.0%~130.0%
0.00~99.99Hz/s
0: disabled;
1: effective during acceleration or deceleration but ineffective at
constant speed, no silencing function;
2: effective all the time, no silencing function;
3: effective during acceleration or deceleration but ineffective at
constant speed, with silencing function;
4: effective all the time, with silencing function.
0~10, 0: disabled
Note: for external device fault, no auto reset function
2.0~20.0s
One's place: action if communication fault
0: alarm and coast to stop
1: not alarm and continue the operation
2: not alarm and stop in specified manner (only for serial port
control mode)
3: not alarm and stop in specified manner (all control modes)
Ten's place: Reserved
2
Hundred's place: E
PROM fault action
0: alarm and coast to stop
1: not alarm and continue the operation
One's place: undervoltage fault indication
0: disabled
1: enabled
Ten's place: auto reset interval fault indication
0: disabled
1: enabled
Hundred's place: fault lockup
0: disabled
1: enabled (without fault indication)
2: enabled (with fault indication)
Thousand's place: output phase loss action
0: disabled
1: enabled
EV1000 Series General Purpose Variable Speed Drive User Manual
Range
Unit
Default
Modification
1
1
0.1%
100.0%
1
1
140.0%
0.1%
120.0%
1
000
130.0%
0.1%
120.0%
0.1s
5.0s
150.0%
0.1%
110.0%
0.01Hz/s
10.00Hz/s
1
2
1
0
0.1s
5.0s
1
001
1
0000
×
×
×
×
×
×
×
×
×
×
×
×
×