62
Appendix 1 Parameter Set
Para.
Name
F2.02
Start freq. hold time
DC brake current at
F2.03
startup
F2.04
DC brake time at startup
F2.05
Acc/Dec mode
F2.06
S curve start time
F2.07
S curve rising time
F2.08
Stop mode
Frequency threshold of
F2.09
DC braking
F2.10
DC brake delay
F2.11
DC brake current
F2.12
DC brake time at stop
F2.13
Dynamic braking
Ration of braking time to
F2.14
total operating time
Para.
Name
F3.00 Anti-reverse setting
F3.01 FWD/REV transition time
F3.02 Reserved
F3.03 Reserved
F3.04 Reserved
F3.05 Auto energy saving
F3.06 AVR function
F3.07 Slip compensation gain
F3.08 Slip compensation limt
F3.09 Compensation time
F3.10 Carrier wave frequency (CWF) 0.7k~15k
F3.11 CWF auto adjustment
F3.12 Motor tone
F3.13 Jog frequency
F3.14 Jog interval
F3.15 Jog Acc time
F3.16 Jog Dec time
F3.17 Acc time 2
F3.18 Dec time 2
F3.19 Acc time 3
F3.20 Dec time 3
F3.21 Acc time 4
F3.22 Dec time 4
Group 2: Start/Brake Parameters
0.0~10.0s
G type:
0.0~150.0% of drive's rated current (max. among phases)
P type:
0.0~130.0%of drive's rated current (max. among phases)
0.0: disabled, 0.1~60.0s
0: linear
10.0%~50.0% (Acc/Dec time)
F2.06+F2.07 ≤ 90%
10.0%~80.0% (Acc/Dec time)
F2.06+F2.07 ≤ 90%
0: decelerate to stop
2: decelerate to stop+ DC brake
0.00~60.00Hz
0.00~10.00s
G type: 0~150% of drive's rated current (max. among the 3 phases) ,
P type: 0~130% of drive's rated current (max. current among the 3
phases) .
0.0: disabled
0.1~60.0s
0: disabled
1: enabled
0.0~100.0%
Group 3: Auxiliary Operating Parameters
0: reverse allowed
0~3600s
-
-
-
0: disabled
0: disabled
2: disabled during decelerating
0.0%~300.0%
0.0%~250.0%
0.1~25.0s
0: Disabled
1: Enabled
0~10
0.10~50.00Hz
0.0~100.0s
0.1~60.0s
0.1~3600 (default unit: S, refer to F9.09)
EV1000 Series General Purpose Variable Speed Drive User Manual
Range
1: S curve
2: auto
1: coast to stop
Range
1: reverse not allowed
1: enabled
1: always enabled
Unit
Default Modification
0.1s
0.0s
0.1%
0.0%
0.1s
0.0s
1
0
0.1%
20.0%
0.1%
60.0%
1
0
0.01Hz 0.00Hz
0.01s
0.00s
0.1%
0.0%
0.1s
0.0s
1
0
0.1%
2.0%
Unit
Default
1
0
0.1s
0.0s
-
0
-
0
-
0
1
0
1
2
0.1%
100.0%
0.1%
200.0%
0.1s
2.0s
10.0kHz (EV1000-
0.1kHz
2S0007G:8kHz
)
1
1
1
0
0.01Hz
5.00Hz
0.1s
0.0s
0.1
6.0s
0.1
6.0s
×
×
×
×
Modification
×
*
*
*
×
×
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents