Emerson EV1000-2S0004G User Manual page 63

General purpose variable speed drive ev1000 series
Hide thumbs Also See for EV1000-2S0004G:
Table of Contents

Advertisement

Para.
Name
Frequency digital
F0.02
setting
F0.03
Control mode
F0.04
Running Direction
F0.05
Max. output freq.
F0.06
Base frequency
F0.07
Max. output voltage
F0.08
Reserved
F0.09
Torque boost
F0.10
Acc time 1
F0.11
Dec time 1
F0.12
Upper limit of freq.
F0.13
Lower limit of freq.
F0.14
V/F curve
F0.15
V/F freq. F3
F0.16
V/F voltage V3
F0.17
V/F freq. F2
F0.18
V/F voltage V2
F0.19
V/Ffreq. F1
F0.20
V/F voltage V1
Manual torque boost
F0.21
cutoff point
Para.
F1.00
Freq. Curve selection
F1.01
Gain of reference frequency selector
F1.02
Filter time
F1.03
Max. input pulse freq.
F1.04
Ratio of Min. input of curve 1 to F1.03
F1.05
Frequency corresponds to min. input of curve 1
F1.06
Ratio of Max. input of curve 1 to F1.03
F1.07
Frequency corresponds to max. input of curve 1 0.00~F0.05
F1.08
Ratio of Min. input of curve 2 to F1.03
F1.09
Frequency corresponds to min. input of curve 2
F1.10
Ratio of Max. input of curve 2 to F1.03
F1.11
Frequency corresponds to max. input of curve 2 0.00~F0.05
Note: All the analog value in the table is shown in volt, it can be converted to current by the formula: V=mA/2.
Para.
Name
F2.00
Start mode
F2.01
Start freq.
Group 0: Basic Operating Parameters
F0.13~F0.12 (when F0.00=0,1,2)
0: LED keypad control
0: Forward
Max {50.00, F0.12}~650.0Hz
1.00~650.0Hz
1~480V
-
0: (auto)
0.1%~30.0%
0.1~3600
(default unit is second, other options refer to F9.09)
F0.13~F0.05
0.00~F0.12
0: user-defined V/F curve, based on F0.15~F0.20
1: curve1, a 2-order curve
2: curve 2, a 1.7-order curve
3: curve 3, a 1.2-order curve
F0.17~F0.06
F0.18~100.0%
F0.19~F0.15
F0.20~F0.16
0.00~F0.17
0~F0.18
0.0~50.0% (based on F0.06)
Group 1: Reference Frequency
Name
Group 2: Start/Brake Parameters
0: start at start frequency (F2.01)
1: brake first and then start at start frequency
Note: start course can refer to the start after first power-on, power
recovery, fault reset and coast to stop.
0.20~60.00Hz
EV1000 Series General Purpose Variable Speed Drive User Manual
Range
1: terminal control
1: Reverse
Range
One's place of F1.00: VCI curve selection
0: curve 1
1: curve 2
Ten's place of F1.00: CCI curve selection
0: curve 1
1: curve 2
Hundred's place of F1.00: PULSE curve selection
0: curve 1
1: curve 2
0.00~9.99
0.01~50.00s
0.1~50.0k
0.0%~F1.06
0.00~F0.05
F1.04~100.0%
0.0%~F1.10
0.00~F0.05
F1.08~100.0%
Range
Appendix 1 Parameter Set
Min unit
Default Modification
0.01Hz
50.00Hz
2: serial port
1
1
0.01Hz
50.00Hz
0.01Hz
50.00Hz
Drive's
1V
rating
-
0.1%
0.0%
0.1
0.01Hz
50.00Hz
0.01Hz
0.00Hz
1
0.01Hz
0.00Hz
0.1%
0.0%
0.01Hz
0.00Hz
0.1%
0.0%
0.01Hz
0.00Hz
0.1%
0.0%
0.1%
10.0%
Unit
Default Modification
1
0.01
0.01s
0.50s
0.1k
10.0k
0.1%
0.0%
1
0.00Hz
0.1%
100.0%
1
50.00Hz
0.1%
0.0%
1
0.00Hz
0.1%
100.0%
1
50.00Hz
Unit
Default Modification
1
0.01Hz 0.50Hz
61
0
0
×
×
×
-
-
6.0s
×
×
0
×
×
×
×
×
×
×
000
1.00
0
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents