Emerson EV1000-2S0004G User Manual page 44

General purpose variable speed drive ev1000 series
Hide thumbs Also See for EV1000-2S0004G:
Table of Contents

Advertisement

42
Chapter 5 Parameters
The signal is given if the preset frequency is higher than
lower limit of frequency and the operating frequency reaches
the lower limit of frequency.
9: Zero-speed running
The signal is given if the drive's output frequency is 0 and
the drive is in operating status.
10: Completion of simple PLC operation stages
The signal is given (pulse, 500ms) if the present stage of
PLC operation is finished.
11: PLC cycle completion indication
The signal (pulse, 500ms) is given if one cycle of PLC
operation is finished.
12: preset counting value arrival
13: reference length arrival
Refer to F7.33~F7.34.
14: preset length arrival
The signal is given if the setting of F9.15 (actual length) is
bigger than F9.14 (preset length) . The length counting
terminal is the one whose parameter (F7.03 or F7.04) is set
at 44.
15: drive ready (RDY)
The RDY signal is output when the drive has no fault, its DC
bus voltage is normal, the Start Prohibit function is disabled.
It is ready to start.
16:Drive fails
The signal is given if the drive has faults.
17: Extended function 1 of host
The output signal of terminal Y1, Y2 or TC is directly
controlled by a serial port. Refer to the communication
protocol of EV1000.
18:Upper and lower limits of traverse frequency.
The signal will be given if the range of traverse frequency
calculated based on central frequency is higher than upper
limit of frequency (F0.12) or lower than the lower limit of
frequency (F0.13) , as shown in Figure5-45.
Upper limit of freq
raverse operation
T
Lower limit of freq.
Y1: upper and lower limit
of traverse operation
Figure 5-45 Limiting the Amplitude of Traverse
19: preset operating time out
The signal is given if the drive's total operating time (Fn.01)
reaches preset operating time (Fn.00) .
Note
When F7.04 is set at 44~46, the pulse output function of Y2 is
disabled automatically.
Before limiting amplitude
After limiting amplitude
Central freq.
EV1000 Series General Purpose Variable Speed Drive User Manual
F7.13 Freq. arrival detection
range (FAR)
As shown in Figure 5-46, if the drive's output frequency is
within the detecting range of preset frequency, a pulse signal
will be output. It is complementary to No.1 function in Table
9-1.
Output
Preset
freq.
Y
Figure 5-46 Freq. Arrival Signal Output
F7.14 FDT1 level
F7.15 FDT1 lag
F7.16 FDT2 level
F7.17 FDT2 lag
F7.14~F7.15 is a complement to the No.2 function in Table
5-9. F7.16~F7.17 is a complement to the No.3 function in
Table 5-9. Their functions are same. Take F7.14~F7.15 for
example: when the drive's output frequency reaches FDT1
level, it outputs an indicating signal until its output frequency
drops below FDT1 level (FDT1 level-FDT1 lag) . As shown in
Figure 5-47.
Output
frequency
FDT1 level
Y
Figure 5-47 Frequency Detection
F7.18~F7.25
These parameters are not used.
F7.26 AO1 output function
F7.27 AO2 output selection
F7.28 Reserved
AO1 and AO2 are analog output terminals.
Refer to section 3.3.2 for the output characteristics of AO1
and AO2, their analog output ranges are defined by F7.29.
Refer to Table 5-10 for the function of F7.26 and F7.27.
Table 5-10 Signals from AO1 and AO2
Setting
Function
Output freq. before
0
compensation
Output freq. after
1
compensation
2
Preset freq.
Range: 0.00~650.00Hz
【 2.50Hz 】
detecting range
Time
Time
Range: 0.00~650.00Hz 【 50.00Hz 】
Range: 0.00~650.00Hz 【 1.00Hz 】
Range: 0.00~650.00Hz 【 25.00Hz 】
Range: 0.00~650.00Hz 【 1.00Hz 】
FDT1 lag
Time
Time
Reserved
Range: 0~12 【 0 】
Range: 0~12 【 3 】
Range
0~max. output freq.
0~max. output freq.
0~max. output freq.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents