Type 8692, 8693 REV.2
EtherNet/IP, PROFINET and Modbus TCP
19.4
Electrical connection
The EtherNet/IP is connected with an M12 circular plug-in connector, 4-pole D-coded.
X7 - M12 field bus connection D-coded:
3
2
Table 49:
Electrical assignment EtherNet/IP
X6 - M12 circular connector, 4-pole:
Pin Wire
color*
1
brown
2
Not used
3
blue
4
Not used
* The indicated colors refer to the connection cable available as an accessory (918038).
Table 50:
X6 - M12 circular connector, 4-pole (operating voltage)
NOTE!
To ensure electromagnetic compatibility (EMC), use a shielded Ethernet cable. Ground the cable
shield on both sides, on each of the connected devices.
For the grounding use a short line (max. 1 m) with a cross-section of at least 1.5 mm
Figure 75:
Functional earth
Pin 1
4
Pin 2
Pin 3
1
Pin 4
Assignment
Operating voltage
+ 24 V DC
Operating voltage
GND
Transmit +
Receive +
Transmit –
Receive –
FE functional earth
.
2
english
169