Central Control Address Setting; Esp Setting (Air Conditioner / General, Dx Ventilator) - LG PREMTB100 Owners & Installation Manual

New standard remote controller
Hide thumbs Also See for PREMTB100:
Table of Contents

Advertisement

INSTALLER SETTING
110
Central control address setting (air conditioner / DX ventilator)
It is the function to set the central control address of the indoor unit to allow communication with
a central controller,
• In the installer setting list, select the central control address setting category, and press [OK]
button to move to the detail screen.
- Select a hex value between 00 and FF.
Value 1: group address setting / value 2: indoor unit address setting
OK

ESP setting (air conditioner / general, DX ventilator)

It is the function to set the fan speed value corresponding to each fan speed for easy installation.
NOTE
!
If ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by the installation specialist that holds an installation license.
For ventilation products, separate ESP values are used for the supply and exhaust fans.
• In the installer setting list, select the ESP setting category, and press [OK] button to move to
the detail screen.
Product
ESP fan speed
Air conditioner
Ventilation
NOTE
!
Be especially careful not to switch ESP values corresponding to each fan speed.
Engineering manuals have ESP setting tables that reference air flow and corresponding
value setting to achieve the flow.
The ESP values that can be set may be different for each product and capacity.
INSTALLER SETTING
OK
value
Slow
Low
Med
High
0 ~ 255
Power
Low
High
Power
111