Setting Guidelines; Directional Negative Sequence Overcurrent Protection - ABB REB670 Applications Manual

Relion 670 series busbar protection
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 370-UUS A
10.1.3
10.1.3.1
Busbar protection REB670 2.2 ANSI
Application manual
There is a risk that the current into the generator at inadvertent energization will be
limited so that the "normal" overcurrent or underimpedance protection will not detect
the dangerous situation. The delay of these protection functions might be too long. The
reverse power protection might detect the situation but the operation time of this
protection is normally too long.
For big and important machines, fast protection against inadvertent energizing should,
therefore, be included in the protective scheme.
The protection against inadvertent energization can be made by a combination of
undervoltage, overvoltage and overcurrent protection functions. The undervoltage
function will, with a delay for example 10 s, detect the situation when the generator is
not connected to the grid (standstill) and activate the overcurrent function. The
overvoltage function will detect the situation when the generator is taken into operation
and will disable the overcurrent function. The overcurrent function will have a pick-up
value about 50% of the rated current of the generator. The trip delay will be about 50
ms.

Setting guidelines

When inverse time overcurrent characteristic is selected, the trip time
of the stage will be the sum of the inverse time delay and the set
definite time delay. Thus, if only the inverse time delay is required, it is
important to set the definite time delay for that stage to zero.
The parameters for the general current and voltage protection function (CVGAPC) are
set via the local HMI or Protection and Control Manager (PCM600).
The overcurrent steps has a IMinx (x=1 or 2 depending on step) setting
to set the minimumpickup current. Set IMinx below PickupCurr_OCx
for every step to achieve ANSI reset characteristic according to
standard. If IMinx is set above PickupCurr_OCx for any step the ANSI
reset works as if current is zero when current drops below IMinx.

Directional negative sequence overcurrent protection

Directional negative sequence overcurrent protection is typically used as sensitive
ground-fault protection of power lines where incorrect zero sequence polarization may
result from mutual induction between two or more parallel lines. Additionally, it can be
used in applications on underground cables where zero-sequence impedance depends
on the fault current return paths, but the cable negative-sequence impedance is
Section 10
Multipurpose protection
GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4
IP15009-1 v2
M13088-237 v3
M13088-3 v5
273