Signals In Single Breaker Arrangement - ABB REB670 Applications Manual

Relion 670 series busbar protection
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 370-UUS A
12.4.7.2
Busbar protection REB670 2.2 ANSI
Application manual

Signals in single breaker arrangement

The busbar grounding switch is only allowed to operate if all disconnectors of the bus-
section are open.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
BB_ES
ABC_LINE
ANSI04000505 V1 EN-US
Figure 170:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnector on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay containing the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and each bus-coupler bay (ABC_BC) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open (AB_TRAFO, ABC_LINE)
22089OTR
289 and 2089 are open (ABC_BC)
789OPTR
789 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
V22089TR
The switch status of 289and 2089 is valid.
VP789TR
The switch status of 789 is valid.
EXDU_BB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
AB_TRAFO
Section 12
Section 2
A2
B2
C
BB_ES
ABC_LINE
en04000505_ansi.vsd
Control
M15053-6 v5
389