Receiving Data - ABB REB670 Applications Manual

Relion 670 series busbar protection
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 17
Station communication
17.2.3.2
476
Application
Generic communication function for Single Point Value (SPGAPC) function is used to
send one single logical output to other systems or equipment in the substation.
SP16GAPC can be used to send up to 16 single point values from the application
functions running in the same cycle time. SPGAPC has one visible input and
SPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for the
monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low
and low-low ranges of the measured value. The actual range of the measured value is
shown on the range output of MVGAPC function block. When a Measured value
expander block (RANGE_XP) is connected to the range output, the logical outputs of
the RANGE_XP are changed accordingly.

Receiving data

The GOOSE data must be received at function blocks. There are different GOOSE
receiving function blocks depending on the type of the received data. Refer to the
Engineering manual for more information about how to configure GOOSE.
Function block type
GOOSEBINRCV
GOOSEINTLKRCV
GOOSEDPRCV
GOOSEINTRCV
GOOSEMVRCV
GOOSESPRCV
GOOSEXLNRCV
1MRK 505 370-UUS A
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v1
Data Type
16 single point
2 single points
16 double points
Double point
Integer
Analog value
Single point
Switch status
Busbar protection REB670 2.2 ANSI
SEMOD55350-5 v8
SEMOD55376-5 v5
SEMOD55402-1 v3
SEMOD55872-5 v10
SEMOD55424-5 v5
Application manual