Ct Disconnection For Bus Interconnector Ct Cores - ABB REB670 Applications Manual

Relion 670 series busbar protection
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 6
Differential protection
6.1.3.6
122
and normally closed (that is, "a" and "b" contacts) auxiliary contacts from the busbar
disconnectors are available to the IED.
If for a particular CT input setting parameter ZoneSel is set to Ctrl_Excludes, then this
CT input will be:
excluded from the differential zone A when input signal CTRLZA on
corresponding bay block is given logical value one and it will be included to the
differential zone A when input signal CTRLZA on corresponding bay block is
given logical value zero
excluded from the differential zone B when input signal CTRLZB on
corresponding bay block is given logical value one and it will be included to the
differential zone B when input signal CTRLZB on corresponding bay block is
given logical value zero.
This setting is typically used for feeder bays in double busbar single breaker stations in
order to form proper busbar disconnector replica. It is especially suitable when only
normally closed (that is, "b" contact) auxiliary contact from the busbar disconnector(s)
is available to the IED. For more information please refer to Figure 64.

CT disconnection for bus interconnector CT cores

For simplicity purpose, sometimes we also refer to a bus-section or bus-coupler bay as
a bus interconnector bay. In practice there are three different solutions for bus
interconnector bay layout. First solution is with two sets of main CTs, which are
located on both sides of the circuit breaker, as shown in Figure 46.
ZA
1
2
8
ANSI01000013 V1 EN-US
Figure 46:
Example of station with two sets of main CTs in the bus-section bay
ZB
BS
1
2
Busbar protection REB670 2.2 ANSI
1MRK 505 370-UUS A
M12113-3 v4
8
en01000013_ansi.vsd
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents