3.1. Case of installing two options
Please install this option (APG001Z) on the top of options when you install two options.
Do not install under the another option.
3.2.
Network cable connection
Connect the APOGEE
Distributed impedance between
Distributed impedance between
* Fix a cable so that a communication connector may be not taken the weight of wire.
®
FLN network cable to communication option as follows.
Title
Wire type
Characteristic impedance
conductors
conductors and shield
Length of a segment
Cable sheath should be peeled off by about 7mm.
For wiring work, use a flat blade screwdriver with a 0.6mm thick and
3.5mm width blade.
Tightening torque for the terminal block is 0.5Nm.
7mm
Description
Shielded twisted cable
Between 100 and 130 ohm
Less than 100pF per meter
Less than 200pF per meter
Foil or braided shield are acceptable.
1200 meters with AWG18 (0.8mm
- 9 -
E6581541②
2
)