Toshiba APG001Z Instruction Manual page 14

Apogee fln option unit
Hide thumbs Also See for APG001Z:
Table of Contents

Advertisement

Example>
<
The example below shows how to configure the VF-PS1 for local/remote operation.
F terminal..................... Operating command
R terminal .................... The APOGEE ® FLN local/remote (Terminal in this example) switching
RR/S4 terminal.......... Operation frequency command
<Wiring>
Variable resistor for adjustment
The APOGEE ® FLN /local Switch
<Parameter setting>
cmod
fmod
f112
<Operation>
R-CC terminal open: VF-PS1 is controlled as a slave device of The APOGEE
R-CC terminal closed:
(Note)
When the local(HAND) / remote key ( f750 = 2 ) is chosen as EASY key selection
and the EASY key lamp of an inverter front panel is on, priority is most given to
operation by a panel. (Refer to the inverter instruction manual for details).
Note that the HAND mode of the panel has priority over FLN local control.
10k ohm
Operation command
(Command mode selection) = 0 (Terminal board)
(Frequency setting mode selection 1) = 2 (RR/S4)
(Input terminal selection 2 (R)) = 48 (Remote/Local control)
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the RR/S4 signal input.
- 13 -
E6581541②
VF-PS1
PP
RR/S4
CCA
SW1
F
SOURCE
SINK
R
CC
®
FLN.