Environmental Type Tests - Siemens RUGGEDCOM RX5000 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX5000:
Table of Contents

Advertisement

Chapter 6
Certification
Oscillatory
HV Impulse
Dielectric Strength

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
36
Description
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
2.5 kV common mode @1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay output)
Test Ad
Test Bd
Test Db
95% (non-condensing), 55 °C (131 °F), 6 cycles
EMC and Environmental Type Tests
RUGGEDCOM RX5000
Installation Guide
Test Levels
+/- 4 kV
+/- 4 kV
5 kV
5 kV
2 kV
2 kV
2 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
2 g @ 10 - 150 Hz
30 g @ 11 mS

Advertisement

Table of Contents
loading

This manual is also suitable for:

A6x30095836

Table of Contents