Chapter 6
Certification
Oscillatory
HV Impulse
Dielectric Strength
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
36
Description
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
2.5 kV common mode @1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay output)
Test Ad
Test Bd
Test Db
95% (non-condensing), 55 °C (131 °F), 6 cycles
EMC and Environmental Type Tests
RUGGEDCOM RX5000
Installation Guide
Test Levels
+/- 4 kV
+/- 4 kV
5 kV
5 kV
2 kV
2 kV
2 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
2 g @ 10 - 150 Hz
30 g @ 11 mS