Switches Sxcbr/Sxswi - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 423-UEN A
8.2.1.3
Bay control REC650 2.2 IEC
Application manual
A request initiates to reserve other bays to prevent simultaneous operation.
Actual position inputs for interlocking information are read and evaluated if
the operation is permitted.
The synchrocheck/synchronizing conditions are read and checked, and
performs operation upon positive response.
The blocking conditions are evaluated
The position indications are evaluated according to given command and its
requested direction (open or closed).
The command sequence is supervised regarding the time between:
Select and execute.
Select and until the reservation is granted.
Execute and the final end position of the apparatus.
Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
In the case when there are three one-phase switches (SXCBR) connected to the
switch controller function, the switch controller will "merge" the position of the
three switches to the resulting three-phase position. In case of a pole discordance
situation, that is, the positions of the one-phase switches are not equal for a time
longer than a settable time; an error signal will be given.
The switch controller is not dependent on the type of switching device SXCBR or
SXSWI. The switch controller represents the content of the SCSWI logical node
(according to IEC 61850) with mandatory functionality.

Switches SXCBR/SXSWI

Switches are functions used to close and interrupt an ac power circuit under normal
conditions, or to interrupt the circuit under fault, or emergency conditions. The
intention with these functions is to represent the lowest level of a power-switching
device with or without short circuit breaking capability, for example, circuit
breakers, disconnectors, earthing switches etc.
The purpose of these functions is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to the primary
apparatus via output boards and to supervise the switching operation and position.
Switches have the following functionalities:
Local/Remote switch intended for the switchyard
Block/deblock for open/close command respectively
Update block/deblock of position indication
Substitution of position indication
Supervision timer that the primary device starts moving after a command
Supervision of allowed time for intermediate position
Definition of pulse duration for open/close command respectively
Section 8
Control
M16602-3 v6
115

Advertisement

Table of Contents
loading

This manual is also suitable for:

RelionRec650

Table of Contents