Example On How To Connect A Star Connected Three- Phase Ct Set To The Ied - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.2.5
L1
CT 600/5
Star Connected
Protected Object
IEC13000002 V4 EN-US
Figure 10:
Star connected three-phase CT set with star point towards the protected object
42
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs
with 1A and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs
with 5A and 10A secondary rating
Example on how to connect a star connected three-phase CT set to
the IED
Figure
10
gives an example about the wiring of a star connected two-phase CT set
to the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the
IED as well.
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
L2
L3
IL1
IL2
IL3
IN
IED
1
2
3
1MRK 511 423-UEN A
SEMOD55055-352 v11
4
SMAI2
BLOCK
AI3P
REVROT
AI1
5
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
IEC13000002-4-en.vsdx
Bay control REC650 2.2 IEC
Application manual