Setting Guidelines; Running Hour-Meter Teilgapc; Identification; Application - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 423-UEN A
10.9.3
10.10
10.10.1
10.10.2
10.10.3
Bay control REC650 2.2 IEC
Application manual
to initiate proceeding actions. The output indicators remain high until the reset of
the function.
It is also possible to initiate the counter from a non-zero value by resetting the
function to the wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue
counting after reaching the maximum count value. The steady overflow output flag
indicates the next count after reaching the maximum count value. It is also possible
to set the counter to rollover and indicate the overflow as a pulse, which lasts up to
the first count after rolling over to zero. In this case, periodic pulses will be
generated at multiple overflow of the function.

Setting guidelines

The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.

Running hour-meter TEILGAPC

Identification

Function Description
Running hour-meter

Application

The function is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is to accumulate the total
running/energized time of the generator, transformer, reactor, capacitor bank or
even line.
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 99999.9 hours. At overflow the accumulated time
resets and the accumulation starts from zero again.
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in hours. The
achievable resolution of the settings is 0.1 hours (6 minutes).
tAlarm and tWarning are independent settings, that is, there is no
check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 99999.9 hours.
IEC 61850
IEC 60617
identification
identification
TEILGAPC
-
Section 10
Monitoring
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v1
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
ANSI/IEEE C37.2 device
number
-
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
223

Advertisement

Table of Contents
loading

This manual is also suitable for:

RelionRec650

Table of Contents