Section 8
Control
8.2.3.4
8.2.3.5
126
The default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a
disconnector (SXSWI).

Proxy for signals from switching device via GOOSE XLNPROXY

The SwitchType setting controls the evaluation of the operating capability. If
SwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breaker
operating capability, otherwise it is interpreted as a switch operating capability.
Table 17:
Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
1
None
2
Open
3
Close – Open
4
Open – Close – Open
5
Close – Open – Close – Open
6
Open – Close – Open – Close – Open
7
more
tStartMove is the supervision time for the apparatus to start moving after a
command execution is done from the SCSWI function. When the time has expired,
the command supervision is reset, and a cause-code is given.
During the tIntermediate time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is
reset, and a cause-code is given. The indication of the mid-position at SCSWI is
suppressed during this time period when the position changes from open to close or
vice-versa if the parameter SuppressMidPos is set to On in the SCSWI function.
In most cases, the same value can be used for both tStartMove and tIntermediate as
in the source function. However, tStartMove may need to be increased to
accommodate for the communication delays, mainly when representing a circuit
breaker.

Bay Reserve (QCRSV)

The timer tCancelRes defines the supervision time for canceling the reservation,
when this cannot be done by requesting bay due to for example communication
failure.
When the parameter ParamRequestx (x=1-8) is set to Only own bay res.
individually for each apparatus (x) in the bay, only the own bay is reserved, that is,
the output for reservation request of other bays (RES_BAYS) will not be activated
at selection of apparatus x.
1MRK 511 423-UEN A
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
Switch operating capability, SwOpCap
None
Open
Close
Close and Open
Larger values handled as 4, both Close and
Open
Bay control REC650 2.2 IEC
M16677-3 v3
Application manual