Control Unit Cabling; Selection Of The Control Cables - Vacon 100 Installation Manual

Wall-mounted drives
Hide thumbs Also See for 100:
Table of Contents

Advertisement

VACON · 90
I.
A DIP switch for the signal selection of
Analogue Input 1
J. The status indicator of the Ethernet
connection
When you receive the AC drive, the control unit contains the standard control interface. If you
included special options in your order, the AC drive will be as in your order. On the next
pages, you will find information on the terminals and general wiring examples.
It is possible to use the drive with an external power source with these properties: +24 VDC
±10%, minimum 1000 mA. Connect the external power source to terminal 30. This voltage is
sufficient to keep the control unit on and for you to set the parameters. The measurements
of the main circuit (for example, the DC link voltage, and the unit temperature) are not
available when the drive is not connected to mains.
The status LED of the drive shows the status of the drive. The status LED is located in the
control panel, below the keypad, and it can show 5 different statuses.
Table 27: The statuses of the status LED of the drive
Colour of the LED light
Blinking slowly
Green
Red
Orange
Blinking fast
6.2

CONTROL UNIT CABLING

The standard I/O board has 22 fixed control terminals and 8 relay board terminals. You can
see the standard connections of the control unit and the descriptions of signals in Fig. 39.
6.2.1

SELECTION OF THE CONTROL CABLES

The control cables must be a minimum of 0.5 mm
the cable types in Table 15 The selection of the correct cable. The terminal wires must be a
maximum of 2.5 mm
Table 28: The tightening torques of the control cables
The terminal
All the terminals of
the I/O board and the
relay board
6
Downloading software
for the relay board terminals and other terminals.
2
The terminal screw
M3
K. A fan (only in IP54 of MR4 and of MR5)
L. The battery for the RTC
M. The location and the default position of
the Safe Torque Off (STO) jumper
Status of the drive
Ready
Run
Fault
Alarm
screened multicore cables. See more on
2
The tightening torque
Nm
lb-in.
0.5
4.5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205