Download Print this page

Emerson Rosemount 0065 Quick Start Manual page 10

Sensor assembly
Hide thumbs Also See for Rosemount 0065:

Advertisement

Quick Start Guide
International
E7
IECEx Flameproof
Certificate: IECEx FMG 12.0022X
Standards: IEC60079-0:2011, IEC60079-1:2007-04
Markings: Ex d IIC T6...T1 Gb, T6(-50 °C ≤ T
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Flameproof joints are not intended for repair.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected to temperature
probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external surface temperature on
the equipment and the neck of DIN Style Sensor probe does not exceed 130 °C.
7. Non-Standard Paint options may cause risk from electrostatic discharge. Avoid
installations that cause electrostatic build-up on painted surfaces, and only clean the
painted surfaces with a damp cloth. If paint is ordered through a special option code,
contact the manufacturer for more information.
Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 13.0535X
Standards: ABNT NBR IEC 60079-0: 2008 + Corrigendum 1:2011; ABNT NBR IEC
Markings: Ex d IIC T6...T1* Gb T6...T1*: (–50 °C ≤ T
Special Conditions for Safe Use (X):
1. See product description for ambient temperature limits and process temperature
limits.
2. The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected to temperature
probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external surface temperature on
the equipment and the neck of DIN Style Sensor probe does not exceed 130 °C.
Japan
E4
Japan Flameproof (0065 only)
Certificate: TC17226
Markings: Ex d IIC T6; (–20 °C ≤ T
Special Condition for Safe Use (X):
1. The wiring shall be suitable for a temperature over 80 °C.
10
60079-1: 2009 + Corrigendum 1:2011
+60 °C)
≤ +40 °C), T5...T1(-50 °C ≤ T
a
≤ +40 °C), T5...T1*:(–50 °C ≤ T
a
≤ +65 °C); Process Temperature: –20 °C to +85 °C
a
August 2017
≤ +60 °C)
a
a

Advertisement

loading

This manual is also suitable for:

Rosemount 0185