Vega VEGAPULS 63 Operating Instructions Manual page 37

4 ... 20 ma/hart
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Extended setting/Quick level
change
Copy sensor data
VEGAPULS 63 - 4 ... 20 mA/HART
Set up with the indicating and adjustment module PLICSCOM
Gating out of false signals
Change now?
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
2 Select the menu item "Service" with [->] and confirm with
[OK]. Now the menu item "False signal suppression" is
displayed.
3 Confirm "False signal suppression - Change now" with
[OK] and select in the below menu "Create new". Enter the
actual distance from the sensor to the product surface. All
false signals in this area are detected by the sensor and
saved after confirming with [OK].
Note:
Check the distance to the product surface, because if an
incorrect (too large) value is entered, the existing level will be
saved as false signal. The filling level would then no longer be
detectable in this area.
The menu item "Extended setting" offers the possibility to
optimise VEGAPULS 63 for applications with quick level
changes. For this purpose select the function "Quick level
change >1 m/min.".
Extended setting
None
Note:
Since with the function "Quick level change >1 m/min." the
generation of an averafy value of the signal processing is
considerably reduced, false reflections by agitators or vessel
installations can cause measured value fluctuations. A false
echo memory is thus recommended.
This function enables reading out parameter adjustment data
as well as writing parameter adjustment data into the sensor
via the indicating and adjustment module. A description of the
function is available in the operating instructions manual
"Indicating and adjustment module".