Vega VEGAPULS 63 Operating Instructions Manual page 16

4 ... 20 ma/hart
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Mounting
Socket
16
Fig. 6: Inflowing liquid
Flush mounting
The optimum installation location of the sensor, also in respect
to the cleanability, is flush on a block flange (flange without
socket piece) or with hygienic fittings, e.g. Neumo Biocontrol.
Mounting on socket
If the reflective properties of the medium are good, you can
mount VEGAPULS 63 on a socket piece. You will find
recommended values for socket heights in the following
illustration. The socket end should be smooth and burr-free, if
possible also rounded. Then carry out a false echo storage.
d
Fig. 7: Deviating socket dimensions
d
50 mm/2"
100 mm
80 mm/3"
150 mm
100 mm/4"
250 mm
150 mm/6"
400 mm
VEGAPULS 63 - 4 ... 20 mA/HART
h
max.