Metering - GE Multilin UR Series N60 Instruction Manual

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
PHASOR MEASUREMENT UNIT
Output format:
per IEEE C37.118 standard
Number of channels:
14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error)
<1%
Triggering:
frequency, voltage, current, power, rate
of change of frequency, user-defined
Reporting rate:
1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60
times per second
Number of clients:
One over TCP/IP port, two over UDP/IP
ports
AC ranges:
As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer or 32-bit IEEE floating
point numbers
Network reporting style: rectangular (real and imaginary) or polar
(magnitude and angle) coordinates
Post-filtering:
none, 3-point, 5-point, 7-point
Calibration:
±5°
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0  CT rating: ±0.25% of reading or ±0.1% of rated
(whichever is greater)
2.0  CT rating:
±1.0% of reading
RMS VOLTAGE
Accuracy:
±0.5% of reading from 10 to 208 V
REAL POWER (WATTS)
Accuracy:
±1.0% of reading at
–0.8  PF  –1.0 and 0.8 PF  1.0
REACTIVE POWER (VARS)
±1.0% of reading at –0.2  PF  0.2
Accuracy:
APPARENT POWER (VA)
Accuracy:
±1.0% of reading
WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
±0 to 1  10
Range:
Parameters:
three-phase only
Update rate:
50 ms
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
6
MWh
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
±0 to 1  10
Range:
Parameters:
three-phase only
Update rate:
50 ms
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
±0.001 Hz (when voltage signal is used
for frequency measurement)
I = 0.1 to 0.25 pu:
±0.05 Hz
I > 0.25 pu:
±0.001 Hz (when current signal is used
for frequency measurement)
DEMAND
Measurements:
Phases A, B, and C present and maxi-
mum measured currents
3-Phase Power (P, Q, and S) present
and maximum measured currents
Accuracy:
±2.0%
2.2 SPECIFICATIONS

2.2.4 METERING

6
Mvarh
2-9
2

Advertisement

Table of Contents
loading

Table of Contents