2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
NOTE
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
2
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE IOC
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0  CT rating: ±0.5% of reading or ±0.4% of rated
> 2.0  CT rating
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timing accuracy:
SENSITIVE DIRECTIONAL POWER
Measured power:
Number of stages:
Characteristic angle:
Calibration angle:
Minimum power:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Time accuracy:
Operate time:
PHASE UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Timing accuracy:
PHASE OVERVOLTAGE
Voltage:
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Operate time:
Timing accuracy:
2-6
0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<16 ms at 3  pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3  pickup at 60 Hz
(Neutral IOC)
Operate at 1.5  pickup
±3% or ±4 ms (whichever is greater)
3-phase, true RMS
2
0 to 359° in steps of 1
0.00 to 0.95° in steps of 0.05
–1.200 to 1.200 pu in steps of 0.001
±1% or ±0.001 pu, whichever is greater
2% or 0.001 pu, whichever is greater
0 to 600.00 s in steps of 0.01
±3% or ±4 ms, whichever is greater
50 ms
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1s base curve)
Time dial = 0.00 to 600.00 in steps of
0.01
Operate at < 0.90  pickup
±3.5% of operate time or ±4 ms (which-
ever is greater)
Phasor only
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 in steps of 0.01 s
30 ms at 1.10  pickup at 60 Hz
±3% or ±4 ms (whichever is greater)
N60 Network Stability and Synchrophasor Measurement System
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup + 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
RATE OF CHANGE OF FREQUENCY
df/dt trend:
increasing, decreasing, bi-directional
df/dt pickup level:
0.10 to 15.00 Hz/s in steps of 0.01
df/dt dropout level:
96% of pickup
df/dt level accuracy:
80 mHz/s or 3.5%, whichever is greater
Overvoltage supv.:
0.100 to 3.000 pu in steps of 0.001
Overcurrent supv.:
0.000 to 30.000 pu in steps of 0.001
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Time accuracy:
±3% or ±4 ms, whichever is greater
95% settling time for df/dt: < 24 cycles
typically 6.5 cycles at 2  pickup
Operate time:
typically 5.5 cycles at 3  pickup
typically 4.5 cycles at 5  pickup
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
0 to 100
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
°