E.2.1 Binary Input Points - GE Multilin UR Series N60 Instruction Manual

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

E.2 DNP POINT LISTS
E.2DNP POINT LISTS
The DNP binary input data points are configured through the
LISTS
BINARY INPUT / MSP POINTS
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.
BINARY INPUT POINTS
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status), Configurable
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable
Change Event Scan Rate: 8 times per power system cycle
Change Event Buffer Size: 500
Default Class for All Points: 1
E
E-8
menu. Refer to the Communications section of Chapter 5 for additional details. When a
N60 Network Stability and Synchrophasor Measurement System

PRODUCT SETUP
COMMUNICATIONS
APPENDIX E

E.2.1 BINARY INPUT POINTS


DNP / IEC104 POINT
GE Multilin