5 SETTINGS

PATH: SETTINGS
CONTROL ELEMENTS
 8-BIT
 COMPARATOR 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This feature allows simple manipulations on 8-bit numbers. In particular two numbers can be added or subtracted depend-
ing on a user-programmable dynamic condition. User-programmable threshold, hysteresis, direction of comparison, pickup
and dropout time delays can be applied.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System


8-BIT COMPARATORS

8-BIT COMPARATOR 1(6)
8BIT COMP 1
FUNCTION: Disabled
8BIT COMP 1 ARG A0:
Off
8BIT COMP 1 ARG A1:
Off
8BIT COMP 1 ARG A7:
Off
8BIT COMP 1 ARG B0:
Off
8BIT COMP 1 ARG B1:
Off
8BIT COMP 1 ARG B7:
Off
8BIT COMP 1 INPUT
MODE: Signed
8BIT COMP 1
DIRECTION: Over
8BIT COMP 1 ADD/SUB:
Off
8BIT COMP 1 PICKUP:
10000.00
8BIT COMP 1
HYSTERESIS: 500.00
8BIT COMP 1 PICKUP
DELAY: 0.000 s
8BIT COMP 1 RESET
DELAY: 0.000 s
8BIT COMP 1 SCALE
FACTOR: 1.00
8BIT COMP 1 BLOCK:
Off
8BIT COMP 1 TARGET:
Self-reset
8BIT COMP 1 EVENTS:
Disabled
5.7 CONTROL ELEMENTS
5.7.13 8-BIT COMPARATORS
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Signed, Absolute
Range: Over, Under
Range: FlexLogic™ operand
Range: –25400.00 to 25400.00 in steps of 0.01
Range: 0 to 5000.00 in steps of 0.01
Range: 0 to 65.353 s in steps of 0.001
Range: 0 to 65.353 s in steps of 0.001
Range: 0.01 to 100.00 in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5