5.2 PRODUCT SETUP
Note that the
ANALOG IN 1 MIN
numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded
NOTE
to the closest possible floating point number.
The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO5 UINTEGER
 CONFIGURATION
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the N60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
5
GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
CONFIGURABLE REPORT 1
 REPORT 1
 DATASET ITEMS
To create the dataset for logical node LN, program the
attributes supported by the N60. Changes to the dataset will only take effect when the N60 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
5-32
and
ANALOG IN 1 MAX

COMMUNICATIONS
GGIO5 UINT In
Off
GGIO5 UINT In
MESSAGE
Off
GGIO5 UINT In
MESSAGE
Off
GGIO5 UINT 1n 16:
MESSAGE
Off

COMMUNICATIONS
REPORT 1 DATASET ITEMS
ITEM
1:
ITEM
2:
MESSAGE
ITEM
3:
MESSAGE
ITEM 64:
MESSAGE
N60 Network Stability and Synchrophasor Measurement System
settings are stored as IEEE 754 / IEC 60559 floating point


IEC 61850 PROTOCOL
Range: Off, any FlexInteger parameter
1:
Range: Off, any FlexInteger parameter
2:
Range: Off, any FlexInteger parameter
3:
Range: Off, any FlexInteger parameter


IEC 61850 PROTOCOL
Range: all valid MMS data item references
Range: as shown above
Range: as shown above
Range: as shown above
to
settings to a value from the list of IEC 61850 data
ITEM 1
ITEM 64
5 SETTINGS
GGIO5 ANALOG CONFIGURATION
REPORT CONTROL CONFIGURATION