5.8 INPUTS AND OUTPUTS
d) APPLICATION EXAMPLE
Direct analog input FlexAnalog parameters (the
in other N60 functions that use FlexAnalog parameters.
The
DIR ANA 1 INTEGRITY
to
FORCED
DIR ANA 32 FORCED
operand can be active (logic 1) at any time. If a direct device is offline, all of the associated trigger operands will be inactive
(logic 0).
The following figure illustrates the operation of the direct analogs feature.
In this example, UR-1 is configured to use four out of its 32 analog channels. These four values are selected from two
sources. UR-2 is configured to receive two out of the four analog values sent, and UR-3 is set to receive three values. Note
that
is effectively being received at both UR-2 and UR-3.
SRC 2 FREQ
5
a) OVERVIEW
PATH: SETTINGS
INPUTS/OUTPUTS
DIRECT INTEGERS
5-194
DIR ANALOG INPUT 1
to
DIR ANA 32 INTEGRITY
FlexLogic™ operands are provided to indicate the most recent trigger condition: Only one
UR-1
SRC1 P
SRC1 PF
Pool of
FlexAnalog
SRC2 FREQ
parameters
SRC1 V1 Mag
UR-2
Remote Analog 7
Pool of
FlexAnalog
parameters
Remote Analog 3
UR-3
Remote Analog 2
Pool of
FlexAnalog
Remote Analog 3
parameters
Remote Analog 9
Figure 5–88: DIRECT ANALOGS SAMPLE APPLICATION
DIRECT INTEGERS
DIRECT INTEGER
OUTPUTS
DIRECT INTEGER
MESSAGE
INPUTS
N60 Network Stability and Synchrophasor Measurement System
to
DIR ANALOG INPUT 32
,
to
DIR ANA 1 DEADBAND
DIR ANA 32 DEADBAND
UR-1 is configured to send four
Analog Out 1
analog values as outputs 1, 2, 3,
and 4, respectively.
Analog Out 2
Analog Out 3
Analog Out 4
TX
RX
UR-2 is configured to receive
Analog In 7
SRC1 P
UR-1 as direct analog inputs 7
and 3, respectively.
Analog In 3
TX
RX
UR-3 is configured to receive
SRC1 PF SRC2 FREQ
SRC1 V1 Mag
Analog In 2
direct analog inputs 2, 3, and 9,
Analog In 3
respectively
Analog In 9
5.8.12 DIRECT INTEGER INPUTS AND OUTPUTS
See page 5–195.
See page 5–195.
5 SETTINGS
values) are available for use
, and
DIR ANA 1
SRC2 FREQ
and
from
,
, and
from UR-1 as
847007A1.CDR
GE Multilin