Table B–9: MODBUS MEMORY MAP (Sheet 26 of 57)
ADDR
REGISTER NAME
7950
PMU Vx Calibration Magnitude
7951
PMU Ia Calibration Angle
7952
PMU Ia Calibration Magnitude
7953
PMU Ib Calibration Angle
7954
PMU Ib Calibration Magnitude
7955
PMU Ic Calibration Angle
7956
PMU Ic Calibration Magnitude
7957
PMU Ig Calibration Angle
7958
PMU Ig Calibration Magnitude
7959
PMU Sequence Voltage Shift Angle
795A
PMU Sequence Current Shift Angle
7983
...Repeated for PMU 2
798D
...Repeated for PMU 3
7997
...Repeated for PMU 4
Phasor Measurement Unit Triggering (Read/Write Setting)
79A1
PMU 1 User Trigger
79A2
...Repeated for PMU 2
79A3
...Repeated for PMU 3
79A4
...Repeated for PMU 4
Phasor Measurement Unit Current Trigger (Read/Write Setting)
79A5
PMU 1 Current Trigger Function
79A6
PMU 1 Current Trigger Pickup
79A7
PMU 1 Current Trigger Pickup Time
79A8
PMU 1 Current Trigger Dropout Time
79A9
PMU 1 Current Trigger Block (3 items)
79AC
PMU 1 Current Trigger Target
79AD
PMU 1 Current Trigger Events
79AE
...Repeated for PMU 2
79B7
...Repeated for PMU 3
79C0
...Repeated for PMU 4
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79C9
PMU 1 df/dt Trigger Function
79CA
PMU 1 df/dt Trigger Raise
79CB
PMU 1 df/dt Trigger Fall
79CC
PMU 1 df/dt Trigger Pickup Time
79CD
PMU 1 df/dt Trigger Dropout Time
79CE
PMU 1 df/dt Trigger Block (3 items)
79D1
PMU 1 df/dt Trigger Target
79D2
PMU 1 df/dt Trigger Events
79D3
...Repeated for PMU 2
79DD
...Repeated for PMU 3
79E7
...Repeated for PMU 4
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
7B61
User Programmable Pushbutton 1 Top Line
7B6B
User Programmable Pushbutton 1 On Text
7B75
User Programmable Pushbutton 1 Off Text
7B7F
User Programmable Pushbutton 1 Drop-Out Time
7B80
User Programmable Pushbutton 1 Target
7B81
User Programmable Pushbutton 1 Events
7B82
User Programmable Pushbutton 1 LED Operand
7B83
User Programmable Pushbutton 1 Autoreset Delay
7B84
User Programmable Pushbutton 1 Autoreset Function
7B85
User Programmable Pushbutton 1 Local Lock
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
95 to 105
%
0.1
-5 to 5
°
0.05
95 to 105
%
0.1
-5 to 5
°
0.05
95 to 105
%
0.1
-5 to 5
°
0.05
95 to 105
%
0.1
-5 to 5
°
0.05
95 to 105
%
0.1
-180 to 180
°
30
-180 to 180
°
30
0 to 65535
---
1
0 to 1
---
1
0.1 to 30
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.1 to 15
Hz/s
0.01
0.1 to 15
Hz/s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 2
---
1
---
---
---
---
---
---
---
---
---
0 to 60
s
0.05
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 600
s
0.05
0 to 1
---
1
0 to 65535
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F002
1000
F002
0
F002
1000
F002
0
F002
1000
F002
0
F002
1000
F002
0
F002
1000
F002
0
F002
0
F300
0
F102
0 (Disabled)
F001
1800
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
25
F001
25
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F109
2 (Disabled)
F202
(none)
F202
(none)
F202
(none)
F001
0
F109
0 (Self-reset)
F102
0 (Disabled)
F300
0
F001
0
F102
0 (Disabled)
F300
0
B-33