5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GENERAL
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
5
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GSEE
GSSE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In N60 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
5-22
COMMUNICATIONS
GENERAL
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
MESSAGE
GOOSE
COMMUNICATIONS
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed N60 GOOSE, and configurable GOOSE.
COMMUNICATIONS
GSSE FUNCTION:
Enabled
GSSE ID:
MESSAGE
GSSEOut
DESTINATION MAC:
MESSAGE
000000000000
setting.
N60 Network Stability and Synchrophasor Measurement System
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: 1 to 60 s in steps of 1
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address