Logical Nodes For Metering And Measurement. Ln Group: M - GE Multilin 850 Communications Manual

Protective relay platform 8 series
Table of Contents

Advertisement

MICS
B-32

2.7 Logical Nodes for metering and measurement. LN Group: M

2.7.1 MMXU (Measurement)
MMXU1: Measurements (845-Slot J, 869, 889-Slot J)
MMXU class
Attribute Name
Attr. Type Explanation
MMXU_1
Data
Common Logical Node Information
Mod
ENC_0
Beh
ENS_0
Health
ENS_1
NamPlt
LPL_1
Measured values
TotW
MV_0
TotVAr
MV_0
TotVA
MV_0
TotPF
MV_0
Hz
MV_0
HzRte
MV_1
Hz3VT
MV_1
Hz3VTRte
MV_1
HzVx
MV_1
HzVxRte
MV_1
PPV
DEL_0
PhV
WYE_0
A
WYE_1
AuxV
CMV_1
MMXU1: Measurements (850)
MMXU class
Attribute Name
Attr. Type Explanation
MMXU_1
Data
Common Logical Node Information
Mod
ENC_0
Beh
ENS_0
Health
ENS_1
NamPlt
LPL_1
Measured values
TotW
MV_0
TotVAr
MV_0
TotVA
MV_0
TotPF
MV_0
Hz
MV_0
CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS
M/O
Measurement
Mode
M
Behavior
M
Health
M
Name plate
M
Total active power (P)
O
Total reactive power (Q)
O
Total apparent power (S)
O
Average power factor (PF) O
Line Frequency
O
Freq. rate of change
O
3 VT Frequency
O
3 VT Freq. rate of change O
Vx Frequency
O
Vx Freq. rate of change
O
Phase to phase voltages
O
(VL1L2,...)
Phase to ground voltages
O
(VL1ER, ...)
Phase currents (IL1, ...)
O
Auxiliary Phase Voltage
O
M/O
Measurement
Mode
M
Behavior
M
Health
M
Name plate
M
Total active power (P)
O
Total reactive power (Q)
O
Total apparent power (S)
O
Average power factor (PF) O
Line Frequency
O
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Notes
Real Power
Reactive Power
Apparent Power
Power Factor
VLFREC
Phase Voltage
Ground Voltage
Currents
Aux Voltage
Notes
Real Power
Reactive Power
Apparent Power
Power Factor
VLFREC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

845889869

Table of Contents