Controllable Enumerated Status (ENC)

Table 3.4.5.18-1 Configurable ENC properties for OPC client
Property/Parameter
Basic
Common Data Class
Addresses
Control Index
Indication Index
Common
Class
Update Rate
Data Class Specific
Control Object
Indication Object
Send All updates
Send As 16 Bit Value
Value or Value range/ Default
ENC
-1...65535
Default: -1
-1...65535
Default: -1
Class 0...3
Default: Class 0
0...65535
Default: 0
Default: Analog control output
block (41).
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
True
False
Default: False
Send as 32 bit value
Send as 16 bit value
Default: Send as 16 bit value
Description
Common data class according
to IEC 61850.
Control index.
Indication index.
Data sent from the slave to the
master can be assigned to four
classes. Data in class 1 is sent
with higher priority than data in
class 3.
Maximum update rate of signal
state changes between the
OPC server and client in milli-
seconds. 0 means that the
server sends all changes to the
client.
Object number for control.
Object number for indication.
Defines whether all changes in
value are send to the master.
Defines whether the value is
sent as 16 or 32 bit value.
49