3.4.5.7.
34
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Parameter
Value or Value range/
Default
Control Object
Default: Analog control
output block (41).
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input
(30, 32)
Send All Updates
True
False
Default: False
Send As 16 Bit Value
Send as 32 bit value
Send as 16 bit value
Default: Send as 16 bit
value
Time And Type Vari-
Send as static data
ation
(always without time)
Event without time
Event with time
Event with relative time
(valid for binary inputs
only)
Default: Event with
time

Complex measured value (CMV)

Table 3.4.5.7-1 Configurable CMV properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
CMV
Class
Addresses
Indication Index
0...65535
Default: 0
Common
Description
Object number for control.
Object number for indication.
Defines if all changes in value are sent to the
master.
Defines if the value is sent as 16 or 32 bit value.
Specifies the type of the timestamp a message
is sent with.
Description
Common data class according to IEC
61850.
Indication index.
1MRS755495