Analog Set Point (Apc) - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS755495
3.4.5.4.
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual

Analog set point (APC)

Table 3.4.5.4-1 Configurable APC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
APC
Class
Addresses
Control Index
-1...65535
Default: -1
Indication Index
-1...65535
Default: -1
Common
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Spe-
cific
Control Object
Default: Analog control output
block (41).
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Send All updates
True
False
Default: False
Send As 16 Bit
Send as 32 bit value
Value
Send as 16 bit value
Default: Send as 16 bit value
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Data sent from the slave to the master can
be assigned to four classes. Data in class
1 is sent with higher priority than data in
class 3.
Maximum update rate of signal state
changes between the OPC server and
client in milliseconds. 0 means that the
server sends all changes to the client.
Object number for control.
Object number for indication.
Defines whether all changes in value are
send to the master.
Defines whether the value is sent as 16
or 32 bit value.
31