Protection Activation Information (Act) - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS755495
3.4.5.3.
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Send As Double
True
Point
False
Default: False
Send As Inverse
True
Value
False
Default: False
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time

Protection activation information (ACT)

Table 3.4.5.3-1 Configurable ACT properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ACT
Class
Addresses
General Index
0...65535
Default: 0
Neutral Index
0...65535
Default: 0
Phase A Index
0...65535
Default: 0
Phase B Index
0...65535
Default: 0
Phase C Index
0...65535
Default: 0
Description
Defines if a value is sent as double point.
Defines if the value of a message is
inverse.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850.
General Index
Neutral Index
Phase A Index
Phase B Index
Phase C Index
29