Integer Controlled Step Position Information; Isc - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.5.13.
42
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Send As 16 Bit
Send as 32 bit value
Value
Send as 16 bit value
Default: Send as 16 bit value
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time
Integer controlled step position information (ISC)
Table 3.4.5.13-1 Configurable ISC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data

ISC

Class
Addresses
Control Index
0...65535
Default: 0
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Spe-
cific
Control Object
Default: Analog control output
block (41).
Description
Defines if the value is sent as 16 or 32 bit
value.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
Maximum update rate of signal state
changes between the OPC server and
client in milliseconds. 0 means that the
server sends all the changes to the client.
Object number for control.
1MRS755495