SITRANS F M
8.6.1

Settings available

8. Commissioning
The transmitter is delivered with factory settings ready to measure the actual flow.
Parameter
Factory settings
Password
Default value
1000
Password
1000
Basic settings
Flow direction
Positive
Q
Dim. dependent
max.
- Volume units
Dim. dependent
- Time units
Dim. dependent
Totalizer 1
Forward
- Totalizer 1 units
Dim. dependent
Totalizer 2
Reverse
- Totalizer 2 units
Dim. dependent
Low flow cut-off
1.5 %
Empty pipe
Off
Error level
Warning
Output
Current output
Off
- Time constant
5 s
Digital output
Pulse
Relay output
Error
Direction/limit switch
Off
- Hysteresis
5%
1)
Batch
Off
- Batch quantity
0
- Batch compensation
0
- Batch counter
Down
- Time constant
0.1 s
Frequency
Off
- Time constant
5 s
Pulse
On
- Pulse polarity
Positive
- Pulse width
66 ms
- Volume/pulse
Dim. dependent
-
Time constant
0.1 s
Electrode cleaning
Off
- Cleaning cycle time
24 h
External input
External input
Off
- Batch
Sensor characteristics
Correction factor
1
Language
English
Operator menu
Primary field
Flow rate
Title/subtitle line
Flow rate
1)
Batch is available on MAG 6000 only
Settings available
1000 ... 9999
Positive, negative
Dim. dependent
3
3
3
m
, ml, l, kl, hl, Ml, ft
, in
, USG, USkG, USMG, UKG,
UKMG, USBBL
Sec., min., hour, day
Forward, reverse, net
3
3
3
m
, ml, l, kl, hl, Ml, ft
, in
, USG, USkG, USMG, UKG,
UKMG, USBBL
Forward, reverse, net
3
3
3
m
, ml, l, kl, hl, Ml, ft
, in
, USG, USkG, USMG, UKG,
UKMG, USBBL
0 ... 9.9 %
Off, on
Fatal, permanent, warning
On/off, uni-/bidirectional, 0/4 - 20 mA
0.1 ... 30 s
1)
Error, direction/limit, batch
, frequency, pulse, error no.,
off
Error, direction/limit, cleaning, error no., off
1 set point/2 set points, −100 ... +100%
0.0 ... 100%
Dim. dependent
−100 ... +100 m
3
Up/down
0.1 ... 30 s
500 Hz, 1 kHz, 5 kHz, 10 kHz
0.1 ... 30 s
Positive/negative
64 µs, 130 µs, 260 µs, 510 µs, 1.0 ms, 2.0 ms,
4.1 ms, 8.2 ms, 16 ms, 33 ms, 66 ms, 130 ms,
260 ms, 520 ms, 1.0 s, 2.1 s, 4.2 s.
Dim. dependent
0.1 ... 30 s
Off/cleaning
1 ... 240 h
Batch, reset totalizer, freeze output, forced output, off
Start, hold/continue, stop, Q
max.
0.85 ... 2.00
English, German, French, Danish, Swedish, Finnish,
Spanish, Russian, Italian, Portuguese and Polish
Flow rate, Totalizer 1, Totalizer 2
Flow rate, Flow rate %, Q
max.
Totalizer 1 reset, Totalizer 2 reset, Batch start/paused/
stop, Batch cycle counter, Batch cycle counter reset,
Sensor size, Sensor type, Error pending, Status log, Tag No.
2
, Totalizer 1, Totalizer 2,
75