Chapter 7. SPECIAL MODULE COMMAND (BUFFER MEMORY READ/WRITE)
7.2.2 Buffer Memory Write –RPUT
<Format>
Symbol
Sl
upper lower
(8 bit) (8 bit)
EF
St
upper lower
(8 bit) (8 bit)
S
D
n
SS
REMARK
To write on buffer memory data of A/D conversion module with RPUT command, configuration the
program
so that execution condition of low(0) will be changed into high(1) at rising edge
(
<ex>
[configuration]
[Buffer memory write]
1) Data on D100 to D138(39 words) of the CPU module device
2) is written onto buffer memory address 0 to 38 of A/D conversion module
3) and store information on the statues of communication to D0000.
[program]
RPUT command
execution condition
RPUT command
execution condition
Descriptions
Upper(AB): the code vale of A/Conversion module
G3F-AD4A: 00h, G3F-AD4B: 0Ah
AB
CD
G4F-AD2A: 80h
Lower (CD): the slot number of communication module
of the master station.
setting range: 0 to 7
Upper(EF): Slot number of A/D conversion module of
remote station.
GH
setting range: 0 to 31
Lower (GH): communication module number of remote
station.
setting range :0 to 63
First address of device which stores write data.
First address of special module which will write data.
Number of words of data write.
Condition data display area of link
). Or not, buffer memory data of A/D conversion module won't be updated
GM3-
K7P-
G3I-
PA1A
30AS
D24A D22A RY4A RY2A FUEA
[RPUT h0A04 h010B D0100 00000 00039 D0000]
RPUT
SI
St
S
D
n
Slot 4
G3I- G3Q- G3Q- G4L-
GM3- G3L- G3I -
G3F-
PA1A RBEA D24A AD4B
Remote station No.11 (0Bh)
7 - 4
SS
Device used
Integer
Integer
M, P, K, L, T, C, D, #D
Integer
Integer, D
M, P, K, L, T, C, D, #D
Slot 1