LG G3F-AD4A User Manual page 78

Programmable logic controller
Table of Contents

Advertisement

Chapter 8. MK PROGRAMMING
Chapter 8. MK PROGRAMMING
8.1 Basic Programming
- This shows the method of operation condition setting for buffer memory in the A/D conversion module.
- The A/D conversion module is mounted on the slot 2.
- A/D conversion module occupies 16 I/O points.
8.1.1 G3F-AD4A
Execution
condition
Execution
condition
The
Buffer
number
Slot
Setting
memory
of word
No.
data.
address
to write
Hexa
decimal
decimal
No. of
Device
Words
to store
to write
8 - 1
Available channel specification
(channel 0,3,4,12)
Data output type specification
(Used channel is specified by
"0" : -192 ~ 16191)
Filter processing enable/disable
specification
(Filter enable : channel 0,3,4)
Filter constant setting
(Filter constant of channel 0,3 : 10)
Filter constant setting
(Filter constant of channel 4 : 50)
Average processing enable/disable
specification
(Average processing enable of
channel 0,3,12)
Number/time average processing
specification
( Channel 0, 3 : time average
Channel 12 : number average)
Number/time average processing
Constant setting of channel 0 to 3
(Time average processing constant
of channel 0 and 3 : 960 ms)
Number/time average processing
Constant setting of channel 12 to 15
(Number
average
processing
constant of channel 12 : 100 count)
Set data specification
(channel 0,3,4,12)
A/D conversion value read
(Data read from addresses 14 ~
29 to D0114 ~ D0129)
Channel operation data read
(Channel in operation will be
read)
Error code read
Channel 0 ~ 3 : read to D131
Channel 4 ~ 7 : read to D132
Channel 8 ~ 11 : read to D133
Channel 12 ~ 15 : read to D134

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G3f-ad4bG4f-ad2a

Table of Contents