Chapter 3. INSTALLATION AND WIRING

3.2.2 Wiring Examples

1)

G3F-AD4A

(1)
Voltage Input
Signal source –10 ~ 10 VDC
(2) Current Input
Signal source –20 ~ 20 mA
*1 For the cable, use a two-core twisted shielded wire.
*2 The SLD terminal and AGND terminal has to be connected.
*3 When there is much noise, the SLD terminal and FG terminal has to be grounded.
*4 Input resistance has been shown.
*5 When there is much noise, FG of the power supply module must be grounded.
Input select switch
Input select switch
3 - 3
Input range switch
Input range switch