Errors On Function Block - LG G3F-AD4A User Manual

Programmable logic controller
Table of Contents

Advertisement

Chapter 4. FUNCTION BLOCK

4.4 Errors on Function Block

This shows errors and resolutions in accordance with them.
STAT
Local
No.
/Remote
0
Operating with no fault
Local
The base location number is exceeding
1
the proper setting range
2
H/W error of the base
The slot location number is exceeding
3
the proper setting range
The A/D conversion module on the slot is
4
empty
5
The module loaded isn't the A/D module
The channel number is exceeding the
6
proper range
7
H/W error of the A/D conversion module
The A/D conversion module's shared
8
memory error
9
The available channels are not specified
10
Test mode
16
Fil t er value exceeding the proper range
Average number/time value exceeding
17
the proper range
H/W error of the communication module
128
Remote
for remote
The base location number is exceeding
129
the proper setting range
The slot location number is exceeding
131
the proper setting range
133
The module loaded isn't the A/D module
135
H/W error of the A/D conversion module
The A/D conversion module's shared
136
memory error
137
The available channels are not specified
138
Test mode
144
Filter value exceeding the proper range
Average number/time value exceeding
145
the proper range
Descriptions
Initiali-za
tion
О
О
О
О
О
О
-
О
О
-
-
О
О
О
О
О
О
О
О
-
-
О
О
4 - 7
Function block
Read
Array
Single
type
type
О
О
Correct the number in accordance with the
proper range
О
О
(See Section 4.2)
Contact the service station
О
О
Set the right number to the slot loading the A/D
О
О
conversion module
Load the A/D conversion module to the specified
О
О
slot
Load the A/D conversion module to the specified
О
О
slot
-
Specify the available channel correctly
О
Contact the service station
О
О
Contact the service station
О
О
Make a correct specification of the available
О
О
channel on the initialize function block
Transmit the test mode to normal mode
О
О
(G4F-AD2A only)
-
-
Correct the value to the range of 1 to 99
Correct the value to the proper range
(Number: 2 to 4,000
-
-
Time: G3F-AD4A, G3F-AD4B 96 to 12,000(ms)
G4F-AD2A 40 to 20,000(ms))
See the manual for the remote communication
О
module
Correct the number in accordance with the
proper range
О
(See Section 4.2)
Set the right number to the slot mounting the
О
A/D conversion module
Mount the A/D conversion module to the
О
specified slot
Contact the service station
О
-
Contact the service station
О
Make a correct specification of the available
О
channel on the initializing function block
Transmit the test mode to normal mode
О
(G4F-AD2A only)
-
Correct the value to the range of 1 to 99
Correct the value to the proper range
(Number: 2 to 4,000
-
Time: G3F-AD4A, G3F-AD4B 96 to 12,000(ms)
G4F-AD2A 40 to 20,000(ms))
Resolutions
-