Operation; Cascade Control - DeDietrich INNOVENS PRO User And Installation Manual

Control panel & control pcb
Table of Contents

Advertisement

7

Operation

7.1

Cascade control

Fig.122
Cascade numbering
A
Fig.123
Traditional cascade control man­
agement
4
+3K
-3K
3
2
1
0
4
8
Fig.124
Parallel cascade control manage­
ment
2
+3K
-3K
1
0
4
8
7667004 - v.01 - 12072017
Up to 7 boilers equipped with the Inicontrol 2 can be managed in cascade
with the Diematic Evolution mounted in the master boiler. The system sen­
sor is connected on the master boiler. All the boilers from the cascade are
connected by a S-BUS cable. The boilers are automatically numbered:
B
C
There are two options for cascade control management:
Adding supplementary boilers successively (traditional control).
Adding supplementary boilers simultaneously (parallel control).
AD-3000964-01
5
6
x
4
8
AD-3000960-01
3
4
Cascade algorithm type temperature, the setpoint sent to the running boil­
er is :
Power; requested by the zones.
Temperature; flow setpoint requested by the zones + error caculation.
Cascade algorithm type power, the setpoint sent to the running boiler is :
x
4
8
AD-3000961-01
Power; accordingly PI algorithms.
Temperature; -90°C
A The master boiler is number 1.
B The first slave boiler is number 3 (number 2 does not exist).
C The second slave boiler is number 4; and so on.
1 First boiler starts running when system temperature is 3°C below
set point.
2 After 4 minutes the second boiler starts running if ΔT< 6K and the
system temperature is still more than 3°C below set point.
3 After 8 minutes the third boiler starts running if ΔT< 6K and the
system temperature is still more than 3°C below set point.
4 First boiler stops running when system temperature is 3°C above
set point.
5 After 4 minutes the second boiler stops running if ΔT< 6K and the
system temperature is still more than 3°C above set point.
6 After 8 minutes the third boiler stops running if ΔT< 6K and the
system temperature is still more than 3°C above set point.
1 All boilers in cascade start running when system temperature is
3°C below set point.
2 First boiler stops running when system temperature is 3°C above
set point.
3 After 4 minutes the second boiler stops running if ΔT< 6K and the
system temperature is still more than 3°C above set point.
4 After 8 minutes the third boiler stops running if ΔT< 6K and the
system temperature is still more than 3°C above set point.