6.3
Wiring Products
Application connector
Use 5-pin open style connectors.
For details on signal layout, refer to the following.
Page 23 Terminal name of terminal block
CAN bus cable
Wire the CAN bus cable that meets the following specifications.
Item
Cable type
Number of pairs
Applicable standard
*1
Wire diameter
Impedance
*1 The maximum wire diameter of the included terminal block is 2.5. To use the cable with wire diameter exceeding 2.5, use a
terminal block suited for the wire diameter of a cable used.
Cable specifications of the CAN bus cable available vary depending on the cable length.
Cable length
0 to 40m
40 to 300m
300 to 600m
600 to 1000m
For compatible CAN bus cables, contact CiA.
For contact information, refer to the following.
www.can-cia.org
Terminating resistor used
In the CANopen network and CAN network, CAN+ and CAN- of the both ends of the network require a terminating resistor at
120 (100 to 130). A 121 1/4W resistor comes with this product.
Description
Shielded twisted pair cable
2
ISO11898
0.2 to 3.3 (24 to 12 AWG)
120 (95 to 140)
Wire diameter
0.25 to 0.34
0.34 to 0.60
0.50 to 0.60
0.75 to 0.80
Resistance per 1m
70m
< 60m
< 40m
< 26m
6 WIRING
6.3 Wiring Products
6
25