6.2
Wiring Products
PROFIBUS devices such as PROFIBUS cables and connectors should be prepared by users. For details on PROFIBUS
devices, refer to the following.
• PI: www.profibus.com
PROFIBUS cable
The following are the specifications and wiring specifications of PROFIBUS cables.
• PROFIBUS cable
Use PROFIBUS cables that satisfy the following specifications (compliant with TypeA (IEC 61158-2)).
Item
Applicable cable
Impedance
Capacity
Conductor resistance
Cross-sectional area
Wire diameter
Type
Material
Temperature rating
• Wiring specifications
RJ71PB91V
RxD/TxD-P
RxD/TxD-N
RxD/TxD-P: Red
RxD/TxD-N: Green
Connectors
Use D-sub 9-pin male connectors for PROFIBUS cables.
Use #4-40 UNC screws for the connector. Tighten the screws within the range of 0.20 to 0.28Nm.
Wiring specifications of terminating resistor
When the RJ71PB91V is the terminal station, use the connector with built-in bus terminator that satisfies the following wiring
specifications.
VP
RxD/TxD-P
RxD/TxD-N
DGND
6 WIRING
30
6.2 Wiring Products
Specifications
Shielded twisted pair cable
135 to 165 (f = 3 to 20MHz)
Less than 30pF/m
Less than 110/km
0.34 or larger
22 AWG
Stranded wire
Copper wire
60 or larger
R
= 390Ω ± 2%, min1/4W
u
R
= 220Ω ± 2%, min1/4W
tA
R
= 390Ω ± 2%, min1/4W
d