BFT RIGEL 5 Installation And User Manual page 6

Universal control unit for operating one or two motors
Hide thumbs Also See for RIGEL 5:
Table of Contents

Advertisement

Enter the numerical value corresponding to the working time from 3 to
180 seconds for motor 2.
2 - Pedestrian operation time (ped. t. ) [6s]
Set the numerical value of the pedestrian opening time from 3 to
90 seconds.
3 - Automatic closing time (tca) [40s]
Set the numerical value of the TCA automatic closing time from 3 to
120 seconds.
4 - Opening delay time for leaf 1 (open delay time) [3s]
Set the opening delay time for motor 1 with respect to motor 2, which can
be adjusted from 0 to 10 seconds.
5 - Closing delay time for leaf 2 (cls delay time) [3s]
Set the closing delay time for motor 2, which can be adjusted from 0 to
60 seconds.
6 - Slow-down time (slow-down t. ) [0s]
Set the end-of-run slow-down time from 0 to 20 seconds.
The slow-down time must be subtracted from the working time.
NOTE: it is advised to activate timing.
NOTE: only use this function when limit switches are fitted.
7 - Traffic-light area clearance time (clear. t) [15s]
Set the required clearance time for the area involved in the traffic governed
by traffic light, from 0 to 30 seconds. Set to 0 if not used.
8 - %Motor torque (mot. torque) [50%]
Set the numerical torque value from 1 to 99%.
NOTE: When using with oil-hydraulic motors, it is necessary to set
the torque value to 99% and adjust the force directly on the motor.
9 - %slowdown motor torque (sloud torque) [50%]
(Advanced parameters ⇒ address 5)
Set numerically from 1% to 99% the value of motor torque during slowdown
time.
10-%Braking (brake) [0%]
Set the required braking percentage from 0 to 99%, compatibly with the
weight of the gate and the existing mechanical stresses.
11-% Emergency braking (emer. brake) [60%]
Set the emergency braking numerical value from 0 to 99%; emergency
braking is carried out by activating the safety controls available at inputs
34 (Lock), 37 (SAFE OP), and 55 (SAFE CL).
12-%Preheating (preheat. ) [30%]
Set the percentage value of the current from 0 (deactivated pre-heating)
to 99% which can be made to pass through the motor windings to keep
them at the right temperature.
13-Zona (Zone) [ 0 ] (Advanced parameters ⇒ address 1)
Enter the zone number between 0 (minimum value) and 127 (maximum
value). See paragraph 14 "Serial connection".
9.2) LOGIC MENU (LOGIC)
- TCA (TCA) [ ON ]
ON: Activates automatic closing
OFF: Excludes automatic closing
- Opening Impulse lock (Ibl open) [ OFF ]
ON: The Start impulse has no effect during the opening phase.
OFF: The Start impulse becomes effective during the opening phase.
- Impulse lock on closing (ibl close) [OFF]
ON: The start impulse has no effect during the closing stage.
OFF: The start impulse is effective during the closing stage.
- Impulse lock TCA (ibl TCA ) [ OFF ]
ON: The Start impulse has no effect during the TCA dwell period.
OFF: The Start impulse becomes effective during the TCA dwell period.
- Ram blow on opening (ram blow c. o p) [OFF]
ON: It pushes for approx. 2 seconds in closing direction before opening.
This allows the electric lock to be released more easily (not affected
by limit switches).
OFF: Excludes the ram blow in closing.
IMPORTANT - When no adequate mechanical backstops are instal-
led, do not use this function. It is also to be absolutely avoided in the
automation of sliding gates.
- Ram blow in closing (ram blow c. c l. ) [OFF]
ON: Before carrying out the closing manoeuvre, the gate pushes for about 2
seconds on opening. This allows the electric lock to be released more
easily.(not affected by limit switches)
IMPORTANT - When no adequate mechanical backstops are instal-
led, do not use this function. It is also to be absolutely avoided in the
automation of sliding gates.
OFF: Excludes the ram blow in closing.
- 2-step, 4-step logic (2 step) [OFF]
ON: Enables 2-step logic (prevails over "3-step logic"). A start impulse has
the following effects:
door closed:...............................................................................opens
on opening:................................................................................closes
door open:.................................................................................closes
on closing:..................................................................................opens
after stopping:............................................................................opens
INSTALLATION MANUAL
OFF:Enables 4-step logic when the 3-step logic is set to OFF. A start impulse
has the following effects:
door closed:...............................................................................opens
on opening:...................................stops and enters TCA if configured
door open:.................................................................................closes
on closing:..................................stops and does not enter TCA (stop)
after stopping:............................................................................opens
- 3-step logic (3 step) [OFF]
ON: Enables 3-step logic (with 2 steps=OFF). A start impulse has the
following effects:
door closed:...............................................................................opens
on opening:...................................stops and enters TCA if configured
door open:.................................................................................closes
on closing:..................................................................................opens
after stopping:............................................................................opens
OFF: Disables 3-step logic.
- Safety edge (bar) [ON]
ON: Input of terminals 36-37 is active as input for the safety edge.
OFF: Input of terminals 36-37 is active as input for opening photocells.
- Pre alarm (pre-alarM) [ OFF ]
ON: The blinker comes on about 3 seconds before the motor starts.
OFF: The blinker comes on at the same time as the motor starts.
- Hold-to-run (hold-to-run ) [ OFF ]
ON: Hold-to-run operation: the manoeuvre continues as long as the command
key is kept pressed. It is not possible to use the radio transmitter.
OFF: Impulse operation: one impulse opens the gate if closed, and closes
it if open.
- Photocells on opening (photc. open) [ OFF ]
ON: In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF: In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.
- Lock hold (bloc persist) [OFF]
ON: If the motors remain still in a totally open or closed position for over one
hour, they are activated for about 3 seconds in the respective direction.
This operation takes place once every hour.
N.B.: This function has the purpose of compensating any oil volume
decrease in the hydraulic motors, due to a temperature drop during
prolonged pauses, for instance at night, or to internal leaks.
IMPORTANT - When no adequate mechanical backstops are instal-
led, do not use this function. It is also to be absolutely avoided in the
automation of sliding gates.
OFF: Excludes the said function.
- Time count (time. c. ) [OFF]
ON: The control unit calculates the activation time of each motor, based on
the preceding manoeuvres.
OFF: The control unit activates the motors at each manoeuvre for the time set.
N.B. Always set the operation time to a slightly higher value than needed
to carry out the complete manoeuvre.
- Rapid closing (fast cls ) [ OFF ]
ON: Closes the gate after photocell disengagement, before waiting for the
end of the TCA (automatic closing time) set.
OFF: Command not entered.
- Clock / Pedestrian (clock ped. ) [OFF]
Input for the connection of an external timer.
ON: The Clock input is only active in Motor 2, for the pedestrian time set.
A start command given during the clock phase carries out complete
gate opening and closing, resetting the open pedestrian position.
OFF: The Clock input acts on both motors.
- Courtesy light (zone light) [OFF]
ON: Zone light. Remains active as long as the manoeuvre lasts.
OFF: Courtesy light. Remains active for 90 seconds after last operation.
N.B. These settings cannot be used if the blinker output is set to ON.
- Blinking output (blink. ) [OFF]
Activate this function only when the SSR5 traffic light-preheating board is present.
ON: Set the output at terminals 12-13 ("courtesy light") as blinking output
(active only during leaf movement).
N.B. Any setting relating to the "courtesy light" function is ignored.
OFF: Keep the output at terminals 12-13 as "courtesy light" or "zone li-
ght".
WARNING! It is not possible to use the SSR5 board in motor preheating mode
and at the same time have the Zone light/Courtesy Light and Blinker/Electric
lock on. In this case, outputs 10-11 cannot be used and outputs 12-13 can
only be used for one of the two functions.
- Light/Alarm (light-alarm) [ON]
ON: Gate-open alarm output (activated if the gate remains open for twice
the TCA time set).
OFF: Stair-light control (the impulse stays on for 1 second).
- 1 active motor (1 mot. on) [OFF]
ON: Only motor 2 activated (1 leaf).
ENGLISH
15
RIGEL 5 - Ver. 08 -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents