(4) File writing
• An existing file cannot be overwritten.
Delete or rename an existing file with the file delete command (delete, mdelete) or the file rename command
(rename) before writing files.
• A read-only file or a file locked by the function except for FTP cannot be written. If attempted, a write error
occurs.
• A file cannot be transferred when the memory card or SD memory card used is protected. If attempted, a
write error occurs.
• A temporary file (FTP_I***.TMP) is automatically created at a file writing. The file is renamed the write target
file name when a writing is completed, however, the temporary file may remain if the CPU module is
powered off or reset during a file writing. In this case, delete the temporary file.
• Before writing or deleting data to the file register in the standard RAM, set the CPU module to STOP.
• When the file register in the standard RAM is set as an auto refresh device, do not perform any writing or
deletion to the corresponding drive.
• When writing a large file to a memory card or SD memory card, set the CPU module to STOP. If writing is
performed in RUN state, a communication error may occur.
(5) File deletion
• The timing for deleting files must be determined by the user, considering the overall system including the
CPU module and programming tool.
• When a memory card or SD memory card is protected, no files can be deleted. An error occurs if a file is
deleted.
(6) Password for FTP
When you forgot the FTP password, set the FTP parameters again by the following steps.
1.
Read out the parameters from the CPU module to the programming tool.
2.
In the FTP Parameter Setting window, click the "Default" button to return all the FTP parameters to
default values.
Project window
3.
Configure the FTP parameter settings again.
4.
Write the parameters to the CPU module from the "Write to PLC" window.
[Online]
5.
Power off and then on or reset the CPU module to enable the parameters.