Specifications; Nv3W - Omron NV Series Setup Manual

Programmable
Hide thumbs Also See for NV Series:
Table of Contents

Advertisement

Specifications

1-4

Specifications

1-4-1

NV3W

General Specifications
Item
Type
Model
Rated power supply
Operating voltage range
Power consumption (current con-
sumption)
Ambient operating temperature
Ambient operating humidity
Ambient storage temperature
Ambient storage humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Resistance to environment
Dimensions
Panel cutout dimensions
Degree of protection
Safety standards
Weight
12
24 V
NV3W-M@20 and NV3W-M@40
24 VDC
21.6 to 26.4 VDC
2 W max. (80 mA max.)
0 to 50°C
20% to 85% (with no condensation)
−20 to 60°C
10% to 85% (with no condensation)
Between the power supply terminals and the case
500 VAC for 1 min with a cutoff current of 10 mA (at initial state)
Between the power supply terminals and the case
100 MΩ (at 500 VDC) (at initial state)
10 to 55 Hz with 0.75-amplitude for 10 min each in X, Y, and Z directions, 1 sweep per
min
2
98 m/s
4 times each in X, Y, and Z directions
with pulse widths of 50 ns and 1 μs between power supply terminals (via
1,000 V
p-p
simulator)
IP65 (at initial state)
Dust proof and drip proof only from the front of the panel (using Waterproof Packing at
the contact surface with the panel)
*Replace the Waterproof Packing each time you reinstall the PT.
110 × 72 × 28 mm (W × H × D)
+1
+1
× 67.0
mm (H × V), Panel thickness: 1.6 to 4.8 mm
105.0
0
0
Operating section on front panel: IP65
UL 508, EC Directives and Korea Certification Mark
160 g max.
Specifications
5 V
NV3W-M@20L
5 VDC
4.5 to 5.5 VDC
1 W max. (200 mA max.)
Section 1-4