PLC Settings
Note
The standard setting in the PLC Setup is Host Link, but the default format is
"7, 2, E," which does not match the settings at the PT. It is therefore necessary
to change the format setting "7, 1, E" so that it matches the settings at the PT.
4. Connect the CX-Programmer online by, for example, selecting Auto Online
from the PLC Menu, and then set the PLC into PROGRAM mode.
5. With the CX-Programmer, select Transfer – To PLC from the PLC Menu.
Select the PLC Setup Check Box and then click the OK Button.
6. A dialog box will be displayed for confirmation. Click the Yes Button. The
transfer will start. When the transfer has been completed, click the OK But-
ton.
Section 6-3
105