Smart Manager
<Correcting duplicate address>
Correct the duplicate address detected through the check using the following procedure.
(1) When the duplicate address check has been completed, select CODE No. C1 with the SET TEMP.
button.
(2) Press the
button.
(3) The number of group in which the error has been detected flashes.
Select the flashing group number to be corrected with the GROUP
(4) Press the
button to clear the set incorrect central control address.
After that, set a correct central control address.
(5) Press the
-EN
18
AMP Air Conditioning
button to terminate the duplicate address correction.
Installation Manual
or
button.