Smart Manager
B Manual setting
Set central control addresses (group numbers) manually from the Smart Manager.
(1) Press the
button and ZONE
(CODE No. C1 flashes.)
(2) Check CODE No. C1, and then press the
(3) Select the line on which the unit exists and the zone and group in which addresses are to be registered with the
LINE button, ZONE
• When a zone is selected, group numbers registered in the zone are displayed.
• Groups whose numbers are displayed are already registered.
• Even when addresses have been registered, the registration can be cancelled with the
(4) Select the unit to be registered in the group selected in step (3).
• Switch refrigeration system No.1 to 31 with the
button.
• When no system exists, indoor unit number is displayed as "- -".
• System number 31 is for a local adapter and heat exchange ventilators. An indoor unit number is always
displayed regardless of whether the unit exists or not.
(5) Press the
button to register the setting or press the
(6) To continue registration, repeat steps (3) to (5).
(7) Press the
button to terminate the address setting.
C Automatic setting
Set central control addresses automatically from the Smart Manager.
(Central control addresses are set automatically in ascending order of unit number.)
(1) Press the
button and ZONE
(CODE No. C1 flashes.)
(2) Press the SET TEMP.
(3) Press the
button. (Central control addresses are automatically registered. This registration requires several
minutes.
(4)
goes out and the indication of C2 flashes, which shows completion of the automatic address
registration.
(5) Press the
button to exit the address setting mode.
<Checking duplicate central control address>
NOTE
This function is not available for light commercial air conditioners.
For details, refer to the manual of the TCC-LINK adapter.
(1) Press the
button and ZONE
(CODE No. C1 flashes.)
(2) Press the SET TEMP.
(3) Press the
button to start checking a duplicate central control address error. (
check.)
(4) When
goes out, the check has been completed.
* When nothing appears in the group number display area at the end of checking, no duplicate address error
has been detected.
* When a group number in the group number display area flashes at the end of checking, a duplicate address
error has been detected.
(Correct the duplicate address.)
AMP Air Conditioning
button simultaneously for at least 4 seconds.
and
buttons, and GROUP
button simultaneously for at least 4 seconds.
or
button to change the CODE No. to C2.
lights during this address setting.)
button simultaneously for at least 4 seconds.
or
button to change the CODE No. C3.
button.
and
button, and then switch indoor unit No.1 to 64 with the
button to cancel the setting.
www.ampair.co.uk | sales@ampair.co.uk
Installation Manual
buttons.
button.
lights during this
EN
-EN
17